A professional solution provider for industrial energy storage and electric vehicle charging piles
12
+years of experience in ESS
31,600
m²industrial park
25,000
m²manufacturing plant
The fault name
phase L1 over voltage
Fault code
105
Number of flashing red lights
1
Troubleshooting and illustration
1.Check the voltage between the AC input line L1 and N.
2.When the voltage between L1 and N exceeds 264V, the fault is reported.
3.Measurement input voltage L1 and N value is about 230V this fault is eliminated.
The fault name
Phase L3 Undervoltage
Fault code
104
Number of flashing red lights
2
Troubleshooting and illustration
1.Check the voltage between the AC input line L2 and N.
2.When the voltage between L2 and N is lower than 190V, the fault is reported.
3.Measurement input voltage L2 and N value is about 230V this fault is eliminated.
The fault name
Phase L3 Undervoltage
Fault code
103
Number of flashing red lights
1
Troubleshooting and illustration
1.Check the voltage between the AC input line L2 and N.
2.When the voltage between L2 and N exceeds 264V, the fault is reported.
3.Measurement input voltage L2 and N value is about 230V this fault is eliminated.
The fault name
Emergency stop press or emergency stop is broken
Fault code
100
Number of flashing red lights
3
Troubleshooting and illustration
1、Find this red button on the side of the charging pile.
2、The emergency stop fault is removed by clockwise rotation.
The fault name
Phase L3 Undervoltage
Fault code
102
Number of flashing red lights
2
Troubleshooting and illustration
1.Check the voltage between the AC input line L3 and N.
2.When the voltage between L3 and N is lower than 190V, the fault is reported.
3.Measurement input voltage L3 and N value is about 230V this fault is eliminated.
The fault name
phase L3 overvoltage
Fault code
101
Number of flashing red lights
1
Troubleshooting and illustration
1.Check the voltage between the AC input line L3 and N.
2.When the voltage between L3 and N exceeds 264V, the fault is reported.
3.Measurement input voltage L3 and N value is about 230V this fault is eliminated.
© 2024 Shenzhen ATESS Power All Rights Reserved. 粤ICP备2023127387号 by GrowthMan